1. What a switchboard is and which standards apply
Quick answer
Power distribution in a building has two levels of boards (QCVN 12:2014/BXD, clauses 1.4.12, 1.4.13). The main distribution board is located at the origin of the supply line into the building. Sub-distribution boards are located after the main board and supply a part of the building. The building entry must have a main distribution board, unless the branch from the overhead line already has a protective device with an operating current not exceeding 25 A (clause 2.1.12.1). After the main board there must be sub-boards for each part of the building (clause 2.1.12.2).
The low-voltage switchgear assembly itself is built to the IEC 61439 series. Part 1 (IEC 61439-1:2020) covers definitions, service conditions, construction requirements, technical characteristics and verification requirements. Part 2 onwards cover specific requirements for each type of assembly (webstore.iec.ch). Part 2 applies to power switchgear and controlgear assemblies with a rated voltage not exceeding 1 000 V a.c. or 1 500 V d.c. Assemblies not covered by Part 3 onwards fall under Part 2. Part 3 covers distribution boards intended to be operated by ordinary persons (DBO).
IEC 61439 separates two responsibilities. The original manufacturer designs the assembly system and carries out design verification by testing, calculation or comparison with a tested reference design. The assembly manufacturer (usually the panel builder) assembles according to the original manufacturer's instructions and carries out routine verification on each assembly. If the assembly departs from the instructions, the design verification must be repeated (Schneider Electrical Installation Guide).
2. Types of boards in a building
The Schneider Electrical Installation Guide classifies low-voltage distribution switchboards by application: main low-voltage switchboard (MLVS, Main LV Switchboard, usually called the MSB in Vietnam), motor control centre (MCC), sub-distribution boards and final distribution boards. Boards for specific applications such as heating, lifts or industrial processes may be located next to the main switchboard or near the point of use. On site, boards are usually named by function as in the table below.
| Board type | Role | Reference |
|---|---|---|
| Main switchboard (MSB) | Located at the point where the supply enters the building; distributes power to the downstream boards | QCVN 12:2014/BXD clause 1.4.12; MLVS in the Schneider EIG |
| Distribution board (DB) | Supplies a part of the building: a floor, an area, an apartment | QCVN 12:2014/BXD clause 1.4.13; sub-distribution and final distribution boards in the Schneider EIG |
| Power board, MCC | Supplies and controls motors such as pumps, fans and machines | MCC trong Schneider EIG |
| Lighting board | Supplies lighting circuits; lighting of staircases, common walkways and corridors must have a separate circuit from the main board | QCVN 12:2014/BXD clause 2.1.14.3 |
| Power factor correction panel | Houses reactive power compensation capacitors; fixed compensation if the capacitor rating does not exceed 15 % of the transformer rating, automatic compensation recommended if larger | Schneider EIG, section on choosing fixed or automatic compensation |
| ATS panel | Automatically transfers the load from the normal supply to the standby supply when the normal supply is abnormal | ABB ACB catalogue, ATS section |
| Safety services board | Supplies safety systems; must be separated from the normal electrical system and be fire-resistant for the specified duration | QCVN 12:2014/BXD clause 2.3.8.6 |
Source: QCVN 12:2014/BXD; Schneider Electric, Electrical Installation Guide, pages "Distribution switchboards" and "The choice between a fixed or automatically-regulated bank of capacitors"; ABB SACE Emax 2 ACB catalogue (undated).
- Flush-mounted boards for apartments and offices: see flush-mounted distribution boards: choosing the size.
- Power factor correction panels: see reactive power compensation panels.
- Power boards: see variable frequency drives for fans and pumps and magnetic contactors and thermal overload relays.
- ATS panels and main circuit-breakers: see when to use an ACB and an ATS.
- Buildings with their own transformer substation receiving medium voltage upstream of the main switchboard: see how to choose 24 and 35 kV medium-voltage cables and medium-voltage cable accessories.
3. IP rating to IEC 60529
The IP code is a numerical classification of the protection provided by an equipment enclosure: against persons touching live parts, against ingress of solid objects and, where indicated, against ingress of water (IEC 60050, clause 426-04-02). The code consists of the letters IP and two characteristic numerals (IEC 60529). The first numeral ranges from 0 to 6, the second from 0 to 8. There is no level 7 for the first numeral, so a code such as IP77 is incorrect. A numeral that need not be specified is replaced by X, for example IPX5 or IP2X. The IP code applies to electrical equipment up to 72.5 kV (Schneider Electrical Installation Guide).
| Numeral | First: solid objects | Second: water |
|---|---|---|
| 0 | Not protected | Not protected |
| 1 | Solid objects of 50 mm and greater | Vertically falling water drops |
| 2 | Solid objects of 12.5 mm and greater | Vertically falling water drops when the enclosure is tilted up to 15° |
| 3 | Solid objects of 2.5 mm and greater | Spraying water, at an angle up to 60° on either side of the vertical |
| 4 | Solid objects of 1.0 mm and greater | Splashing water from any direction |
| 5 | Dust-protected: ingress of dust is not sufficient to interfere with operation or safety | Water jets from any direction |
| 6 | Dust-tight: no ingress of dust | Powerful water jets from any direction |
| 7 | No such level | Temporary immersion in water, pressure and duration as specified in the standard |
| 8 | No such level | Continuous immersion in water, conditions agreed between manufacturer and user, more severe than level 7 |
Source: IEC 60529 (edition 2.1, 2001), tables of the first characteristic numeral (solid objects) and the second (water), copy of the standard republished by wewontech.com.
- IPX7, IPX8 (immersion) do not include IPX5, IPX6 (water jets). An enclosure that withstands both must carry a dual marking, for example IPX5/IPX7 (IEC 60529).
- Protection against access to hazardous parts also has additional letters A, B, C, D after the two numerals: B is a test finger 12 mm in diameter and 80 mm long; D is a test wire 1.0 mm in diameter and 100 mm long (IEC 60529).
- Barriers and enclosures for protection against direct contact must have a minimum degree of protection of IPXXB or IP2X, and IPXXD or IP4X on readily accessible top horizontal surfaces (QCVN 12:2014/BXD, clause 2.4.1.2).
- Where an enclosure has several mounting arrangements giving different IP ratings, the manufacturer must state the IP rating for each mounting arrangement in the instructions (IEC 60529).
4. IK impact protection rating to IEC 62262
IEC 62262 defines the IK code, which indicates the ability of an equipment enclosure to withstand mechanical impacts on all sides. The code consists of the letters IK and two numerals from 00 to 10, corresponding to the impact energy in joules (J). The AG column is the mechanical stress code in the classification of external influences of IEC 60364-5-51 (Schneider Electrical Installation Guide).
In IEC 61439, mechanical impact (clause 10.2.6) and the degree of protection of enclosures (clause 10.3) are both part of the assembly design verification list. Mechanical impact may only be verified by testing (Schneider Electrical Installation Guide, figure E34).
| IK code | Impact energy | Corresponding AG code |
|---|---|---|
| IK00 | 0 J | — |
| IK01 | ≤ 0,14 J | — |
| IK02 | ≤ 0,20 J | AG1 |
| IK03 | ≤ 0,35 J | — |
| IK04 | ≤ 0,50 J | — |
| IK05 | ≤ 0,70 J | — |
| IK06 | ≤ 1 J | — |
| IK07 | ≤ 2 J | AG2 |
| IK08 | ≤ 5 J | AG3 |
| IK09 | ≤ 10 J | — |
| IK10 | ≤ 20 J | AG4 |
Source: Schneider Electric, Electrical Installation Guide, page "Protection provided for enclosed equipment: codes IP and IK", figure E68.
5. Choosing IP and IK by board location
The IP and IK ratings of the enclosure are chosen according to the external influences defined in IEC 60364-5-51: presence of solid objects (code AE), presence of water (code AD), mechanical stress and capability of persons with access (code BA). Unless national regulations state otherwise, Schneider recommends the values in the table below for indoor switchboards (Schneider Electrical Installation Guide).
| Location | Conditions | IP | IK |
|---|---|---|---|
| Technical room | Normal, no vertically falling water; no risk of major impact | IP30 | IK07 |
| Corridor | Normal, risk of vertically falling water; risk of significant impact that could damage equipment | IP31 | IK08 (enclosure with door) |
| Workshop | Very severe, risk of water splashing from any direction; highest risk of impact that could damage the enclosure | IP54/55 | IK10 |
Swipe sideways to see all columns.
Source: Schneider Electric, Electrical Installation Guide, figures E69, E70. The example in the source is the Prisma switchboard range, designed for indoor installation; national regulations take precedence.
- Do not install switchboards below or inside toilets, bathrooms, washing areas, laundry rooms or rooms containing chemicals (QCVN 12:2014/BXD, clause 2.1.12.8).
- In areas with high occupancy density (referred to in QCVN as KV2, KV3), switching, control and protective devices must be arranged so that only authorised persons have access. If located within walkways, they must be housed in closed boards or boxes made of non-combustible or low-combustibility material (QCVN 12:2014/BXD, clauses 2.5.3.2, 2.5.3.3).
6. Enclosure materials
IEC 61439 verifies the strength of assembly materials through the following items: resistance to corrosion (clause 10.2.2), properties of insulating materials including thermal stability and resistance to abnormal heat and fire due to internal electrical effects (10.2.3), resistance to ultraviolet (UV) radiation (10.2.4), mechanical impact (10.2.6). Resistance to corrosion may only be verified by testing, not by calculation or comparison (Schneider Electrical Installation Guide, figure E34, based on Table D.1 of Annex D of IEC 61439-1).
For small distribution boards, the Sino Vanlock enclosure catalogue (undated) shows the following material options:
- E4M flush-mounted boards: white or clear smoked cover, plastic or steel base.
- Flush-mounted boards with ABS plastic front and polycarbonate (PC) cover.
- Metal enclosures with PC protective cover, flush-mounted or surface-mounted, by number of modules (for example 28, 36, 48 modules).
- Waterproof metal enclosures, rated IP65/55 in the catalogue.
- Metal enclosures for housing MCCBs and magnetic contactors.
7. Forms of separation and functional unit types
An assembly is divided into functional units. Each unit comprises all the electrical and mechanical elements that together perform one function. An assembly has one incoming unit and one or more outgoing units. IEC 61439 specifies the forms of separation between these units, numbered from 1 to 4, with variants a or b. A higher form number includes the features of the lower numbers. The choice of form is agreed between the assembly manufacturer and the user (Schneider Electrical Installation Guide).
| Form | Separation |
|---|---|
| Form 1 | No separation |
| Form 2 | Busbars separated from functional units |
| Form 3 | As form 2, plus functional units separated from each other, except outgoing terminals |
| Form 4 | As form 3, plus outgoing terminals of functional units separated from each other |
Source: Schneider Electric, Electrical Installation Guide, page "Distribution switchboards", section Forms. For details of variants a and b, see IEC 61439-2.
- For forms higher than 1, all parts in a functional unit that remain live when that unit is disconnected must be covered to at least IPXXB (IEC 61439-2:2020, abstract on webstore.iec.ch).
- Functional units come in three types: fixed (maintenance requires shutting down the whole assembly); removable (mounted on a removable base plate, with isolation on the busbar side and the outgoing side); withdrawable drawer (a faulty unit can be replaced quickly without de-energising the rest of the assembly) (Schneider Electrical Installation Guide).
- Replacing devices in the assembly with devices of another brand or range affects the temperature-rise verification and the short-circuit withstand capability. Under IEC 61439, the assembly keeps its verified performance only when devices are replaced with devices of the same brand and range with equal or better limiting characteristics (I²t, Ipk). Replacement with another brand must be verified by testing (Schneider Electrical Installation Guide).
- Selecting circuit-breakers and disconnectors for each unit: see selecting switchgear for low-voltage switchboards.
- When requesting a switchboard, state: board type, voltage, rated current, short-circuit current at the board, location, IP, IK, form, functional unit type and equipment list. For how to prepare the list, see preparing a BOQ for a fast quotation.
Sources and scope
- QCVN 12:2014/BXD clauses 1.4.12, 1.4.13, 2.1.12.1, 2.1.12.2, 2.1.12.8, 2.1.14.3, 2.3.8.6, 2.4.1.2, 2.5.3.2, 2.5.3.3
- IEC 60050 clause 426-04-02
- IEC 60529 edition 2.1 (2001), copy republished by wewontech.com (accessed 14/10/2026)
- IEC 61439-1:2020 and IEC 61439-2:2020, abstracts on webstore.iec.ch (accessed 14/10/2026)
- Schneider Electric, Electrical Installation Guide, pages "Distribution switchboards", "Protection provided for enclosed equipment: codes IP and IK", "The choice between a fixed or automatically-regulated bank of capacitors" (accessed 14/10/2026)
- ABB SACE Emax 2 ACB catalogue (undated)
- Sino Vanlock enclosure catalogue (undated). Compiled by Hoang Nhat
- not a substitute for design and calculation by an engineer