Factory lighting: selecting luminaires by TCVN 7114-1 illuminance and ceiling height

Select the illuminance level from the TCVN 7114-1:2008 table for the correct area of the factory, warehouse or ancillary room, together with the requirements for uniformity, glare and colour rendering. Then choose the luminaire type by environment and mounting height; factories with luminaires mounted above 6 m have a specific exception for colour rendering.

Author
Compiled by Hoang Nhat
Updated
14/10/2026
Reading time
6 min
Reference tables
3 sourced tables
  • TCVN 7114-1:2008
  • TCVN 9207:2012
Contents (6 sections)
  1. In what order to select luminaires
  2. The four criteria of TCVN 7114-1
  3. Illuminance for production areas
  4. Warehouses, circulation areas, ancillary rooms
  5. High-ceiling workshops above 6 m
  6. Choosing the luminaire type by area

In what order to select luminaires

Quick answer

For indoor work places, TCVN 7114-1:2008 specifies four criteria for each type of area and task: maintained illuminance, uniformity, UGR glare limit and colour rendering index Ra. First, select the level from the table in Clause 5 for the correct area. Then choose the luminaire type according to the environment (dust, humidity, mounting height), and calculate the number of luminaires in the lighting design documents. For emergency lighting see exit signs and emergency luminaires; for luminaires in damp or dusty areas see waterproof, dustproof and explosion-proof luminaires.

TCVN 7114-1:2008 is identical to ISO 8995-1:2002/Cor 1:2005. The standard sets out requirements and does not give guidance on how to design the lighting system for each specific location (Clause 1); the number of luminaires, their wattage and layout are still calculated by the design engineer.

The four criteria of TCVN 7114-1

All illuminance values in the standard are maintained illuminance: the average illuminance on the working surface must not fall below the value in the table at any time during use, including after the luminaires have lost luminous flux and become soiled. The standard therefore requires a design maintenance factor of not less than 0.7 (clause 4.8).

Lighting criteria for indoor work places
CriterionRequirementClause
Maintained illuminance EmNot less than the value in Clause 5; not below 200 lux for continuously occupied work places. May be raised or lowered by at least one step on the scale where visual conditions differ from those assumed4.3, 4.3.1
Illuminance scale20 – 30 – 50 – 75 – 100 – 150 – 200 – 300 – 500 – 750 – 1000 – 1500 – 2000 – 3000 – 5000 lux4.3.2
Uniformity Uo (Emin/Eav)Task area ≥ 0.7; immediate surrounding area ≥ 0.54.3.4
Glare UGRThe UGR of the installation must not exceed UGR_L in Clause 5; scale 13 – 16 – 19 – 22 – 25 – 28 (the lower the number, the stricter)4.4.2
Colour rendering RaLamps with Ra < 80 should not be used for regularly occupied work places, except in high-ceiling workshops with luminaires mounted above 6 m (see the section below)4.6.2
Maintenance factorNot less than 0.74.8

Source: TCVN 7114-1:2008 Clause 4; full-text republication, cross-checked against two or more sources.

  • Immediate surrounding area: 500 lux where the task area illuminance is 750 lux or more; 300 lux where it is 500 lux; 200 lux where it is 300 lux; at 200 lux or below, equal to the task area illuminance (table in clause 4.3.3).

Illuminance for production areas

The table in Clause 5 is divided by industry and process. The rows most often encountered in mechanical and electrical workshops:

Lighting requirements for selected production tasks
Area, taskEm (lux)UGR_LRa
Production machinery with frequent manual operation3002580
Forging, welding, bench fitting3002560
Rough and medium machining (tolerance > 0.1 mm)3002260
Precision machining (tolerance < 0.1 mm)5001960
Mechanical assembly workshop: coarse parts2002580
Mechanical assembly workshop: medium parts3002580
Mechanical assembly workshop: small parts5002280
Mechanical assembly workshop: precision work7501980
Surface treatment and painting7502580
Cable manufacturing; winding of large coils3002580
Electrical equipment assembly: medium parts (e.g. switchboards)5002280
Electrical equipment assembly: precision parts (e.g. measuring instruments)10001680
Electronics workshops, testing, adjustment15001680

Swipe sideways to see all columns.

Source: TCVN 7114-1:2008, table in Clause 5, groups 6 (general production), 7 (electrical industry), 14 (metalworking); full-text republication, all cells consistent across sources.

Warehouses, circulation areas and ancillary rooms

Ancillary areas in a factory have lower levels, but where people work regularly the level must still be raised according to the notes in the table.

Lighting requirements for general areas, warehouses and ancillary rooms
AreaEm (lux)UGR_LRaNotes in the standard
Circulation areas, corridors1002840Provide a transition zone at entrances
Stairs1502540—
Warehouses, cold stores1002560200 lux if continuously occupied
Packing and dispatch areas3002560—
Control stations1502260200 lux if continuously occupied
Switchgear rooms2002560—
Cloakrooms, bathrooms, toilets2002580—
Canteens1502540—
General offices5001980—

Swipe sideways to see all columns.

Source: TCVN 7114-1:2008, table in Clause 5, groups 1 (general areas) and 22 (offices).

  • The table has no separate row for high-rack warehouses; the value for high-rack warehouses is taken from the project design documents, not inferred from the "warehouses" row.
  • Plants with a control room: the standard lists a control room row only in the power station group (500 lux, UGR 16, Ra 80); for other factories, refer to the design documents.

High-ceiling workshops: luminaires mounted above 6 m

TCVN 7114-1:2008 (clause 4.6.2) allows an exception on colour rendering for high-ceiling workshops and outdoor lighting with industrial luminaires mounted above 6 m: Ra ≥ 80 is not mandatory as it is for other interiors where people work or stay for long periods. Nevertheless, measures must still be taken to provide high colour rendering lighting at continuously occupied work places and at locations where safety colours must be clearly recognised. Many rows in the table marked "high-ceiling workshops see 4.6.2" refer precisely to this exception.

The higher the mounting height, the harder it is to achieve a uniformity of 0.7 on the working surface with few luminaires; the number of luminaires, beam angles and spacing are calculated in lighting design software using the photometric data of the exact luminaire model, not inferred from wattage.

Choosing the luminaire type by area

Once the required illuminance level is known, the luminaire type is chosen by mounting height and environment. The industrial luminaires category is divided into high-bay luminaires for high-ceiling workshops, LED floodlights and industrial reflector luminaires; office and ancillary areas use LED luminaires such as tubes and panels.

Sources and scope

  • TCVN 7114-1:2008 (ISO 8995-1:2002/Cor 1:2005) Clause 1, clauses 4.3, 4.3.1–4.3.4, 4.4.2, 4.6.2, 4.8 and the table in Clause 5 — full-text republication, cross-checked against two or more sources, validity status checked on 14/10/2026
  • TCVN 9207:2012 Table 9. Compiled by Hoang Nhat
  • not a substitute for lighting design