Selecting low-voltage cables for building projects: steps and TCVN standards

Six steps for selecting low-voltage cables for a project according to TCVN 9207:2012, TCVN 7447-5-52:2010 and QCVN 12:2014/BXD: cable type, load current, cross-sectional area, voltage drop, neutral and PE conductors, fire requirements.

Author
Compiled by Hoang Nhat
Updated
14/10/2026
Reading time
7 min
Reference tables
2 sourced tables
  • TCVN 9207:2012
  • TCVN 7447-5-52:2010
  • QCVN 12:2014
  • TCVN 9206:2012
  • TCVN 5935-1:2013
  • TCVN 6610-1:2014
Contents (8 sections)
  1. Order of selection
  2. 1. Cable type
  3. 2. Design current
  4. 3. Cross-sectional area
  5. 4. Voltage drop
  6. 5. Neutral and PE conductors
  7. 6. Fire requirements
  8. When ordering

In what order to select a cable

Quick answer

First, choose the cable type that suits the voltage and the installation location. Next, select the cross-section by the permissible heating condition, then check it against voltage drop and coordination with the protective device. This is the sequence TCVN 9207:2012 sets out in clause 10.1. Finally, check the neutral conductor, the protective conductor and the fire requirements. Each step has its own article:

The table below shows which document applies at which step. QCVN 12:2014/BXD is a mandatory regulation, but it applies only to electrical systems of residential and public buildings. For factory buildings, refer to the standards adopted in the project design documents.

Documents used when selecting low-voltage cables
DocumentContent used in cable selectionStep
TCVN 9207:2012Cross-section selection sequence (10.1); minimum cross-sections (Table 2); voltage drop (Table 9); PE conductors (Table 12); cables for fire-safety loads (5.3)1, 3, 4, 5, 6
TCVN 7447-5-52:2010 (IEC 60364-5-52:2009)Current-carrying capacity tables by installation method, correction factors for temperature and grouping; Annex G on voltage drop3, 4
QCVN 12:2014/BXDMinimum cross-sections (2.1.5), 5 % voltage drop (2.1.7), reduced fire spread (2.1.9), overload protection IB ≤ In ≤ Iz (2.6.3)3, 4, 5, 6
TCVN 9206:2012Design load; supply voltage 380/220 V (4.2); voltage loss at equipment terminals (4.5)2, 4
TCVN 5935-1:2013 (IEC 60502-1:2009)Power cables with extruded insulation, rated voltages 1 kV and 3 kV1
TCVN 6610Wires and cables with PVC insulation up to 450/750 V1
IEC 60228 (TCVN 6612)Series of nominal cross-sections, conductor resistance1, 3

Swipe sideways to see all columns.

Source: scope and clauses taken from the documents listed in the table; compiled by Hoang Nhat.

1. Select the cable type by voltage, installation location and environment

Low-voltage power cables with extruded insulation such as CVV and CXV are rated 0.6/1 kV and fall within the scope of TCVN 5935-1:2013. Wires and cables with PVC insulation to TCVN 6610 have rated voltages up to 450/750 V. The insulation material determines the maximum operating temperature of the conductor: 70 °C for PVC, 90 °C for XLPE (TCVN 7447-5-52:2010, Table 52.1). Therefore, for the same cross-section and installation method, an XLPE cable carries a higher current.

The insulation must suit the supply voltage, the installation method and the environmental conditions (TCVN 9207:2012, clause 5.4). The wiring system type is also chosen by environment (Table 5 of this standard). For example, in damp and very damp locations and outdoors, steel conduit and closed steel trunking with a conduit or trunking wall thickness of 2 mm or less are prohibited. For the designation of each cable type, see how CV, CVV, CXV and DSTA differ. Cable ranges are listed in the low-voltage copper cables and low-voltage aluminium cables categories.

2. Determine the design current IB

The design current IB is taken from the load calculation. Under TCVN 9206:2012, the supply voltage to equipment in residential and public buildings (except motors) shall not exceed 380/220 V (clause 4.2). The design power factor of residential networks is taken as 0.80 to 0.85 (clause 5.8). How to convert power to current, with a table of current by power, is covered in how to size cables by power.

3. Select the cross-section by current-carrying capacity, then compare with the minimum cross-section

Select the smallest size whose corrected current-carrying capacity is not less than IB. The current-carrying capacity is looked up by conductor material, insulation, number of loaded conductors and installation method, then multiplied by the temperature and grouping factors. Look it up in the cable current-carrying capacity tables or enter the values in the cable size calculator. TCVN 9207:2012 (clause 10.2) gives priority to values declared by the manufacturer. The tables of TCVN 7447-5-52 are used only when the manufacturer does not specify them.

The selected cross-section shall not be smaller than the minimum cross-section for each type of circuit given in the table below.

Minimum conductor cross-sections of wires and cables (mm²)
CircuitCopperAluminium
Lighting circuits without socket-outlets1,52,5
Lighting circuits with socket-outlets; socket-outlet circuits2,54
Power distribution2,54
From floor distribution board to room distribution boards46
Risers supplying one or several floors610

Source: TCVN 9207:2012, Table 2. QCVN 12:2014/BXD clause 2.1.5.1 specifies the same values for phase conductors and adds 0.5 mm² for signalling and control circuits.

  • The cable must be protected against overload according to IB ≤ In ≤ Iz (QCVN 12:2014/BXD, clause 2.6.3.1). For how to select the circuit-breaker, see selecting an MCB by load current.
  • Current-carrying capacity shall be determined for the section of the route with the poorest heat dissipation, except for wall penetrations shorter than 0.35 m (QCVN 12:2014/BXD, clause 2.1.4.6).

4. Check the voltage drop to the most distant equipment

In residential and public buildings, the voltage drop from the origin of the supply to any equipment shall not exceed 5 % of the nominal voltage (QCVN 12:2014/BXD, clause 2.1.7). TCVN 9207:2012 (Table 9) also takes 5 % for lighting, motors and other loads, and 10 % for 12–42 V equipment. On long runs, the cross-section often has to be increased because of voltage drop rather than load current. Calculation method and examples are in permissible voltage drop and how to calculate it. For a quick result, use the voltage drop calculator.

5. Neutral conductor and PE protective conductor

The neutral conductor must be equal to the phase conductor in single-phase two-wire circuits and in three-phase circuits with phase conductors up to 16 mm² (QCVN 12:2014/BXD, clause 2.1.5.2). The neutral may be smaller than the phase conductor only when all conditions are met: the phase conductor is larger than 16 mm², the load is balanced, 3rd harmonic content does not exceed 15 % and the neutral conductor is protected against overcurrent. Even then, the neutral must not be less than 50 % of the phase conductor and not less than 16 mm². How to read a 3-phase + 1 neutral cable designation is explained in reading cable designations and specifications under TCVN.

The PE conductor is of the same metal as the phase conductor, with its cross-section according to TCVN 9207:2012 (Table 12):

  • Phase conductor S ≤ 16 mm²: PE equal to S.
  • 16 < S ≤ 35 mm²: PE 16 mm².
  • 35 < S ≤ 400 mm²: PE equal to S/2.
  • PE conductor not forming part of the supply wiring system: minimum 1.5 mm² if protected against mechanical damage, 4 mm² if not (TCVN 9207:2012, clause 10.11).

6. Fire requirements

Wires and cables supplying fire-fighting and evacuation loads must have a sheath of fire-resistant material (TCVN 9207:2012, clause 5.3). These loads include exit lighting, central processing units for fire alarm and automatic fire suppression, fire pumps, stairwell pressurisation fans and lifts. Where the building requires reduced fire spread, QCVN 12:2014/BXD (clause 2.1.9.1) requires materials that minimise the risk of fire spread. How fire-resistant cables differ from flame-retardant cables is explained in fire-resistant and flame-retardant cables. Cable ranges are listed in the fire-resistant and flame-retardant cables category.

When ordering

For each run, state the cable designation, number of cores × cross-section, voltage rating, brand and length in metres. Specify clearly which runs require armour, fire-resistant or flame-retardant cable. Certification documents differ by brand and product, so state your requirements when you send the list. A sample cable line entry is in preparing a BOQ to receive a quotation.

Hoang Nhat is an authorised dealer of Cadi-Sun, an official distributor of GoldCup and a distributor of TAYA; other cable groups are listed in the wires and cables category.

Sources and scope

  • TCVN 9207:2012 clauses 5.3, 5.4, 10.1, 10.2, 10.11, Tables 2, 5, 9, 12
  • TCVN 7447-5-52:2010 Table 52.1
  • QCVN 12:2014/BXD clauses 2.1.4.6, 2.1.5, 2.1.7, 2.1.9.1, 2.6.3.1
  • TCVN 9206:2012 clauses 4.2, 5.8
  • TCVN 5935-1:2013
  • TCVN 6610-1:2014
  • IEC 60228:2004. Compiled by Hoang Nhat
  • not a substitute for electrical design